9V DC MTL5511 MTL Safety Barrier Switch Proximity Detector Interface

Place of Origin UK
Hàng hiệu MTL
Chứng nhận ROHS
Model Number MTL5511
Chi tiết sản phẩm
Color:
White and blue
material:
plastic and metal
Shipping Weight:
1.0Kg
Dimensions ( D x W x H ):
1.58 cm x 10.98 cm x 12.36 cm
Number of channels:
One
Voltage applied to sensor:
7 to 9V dc from 1kO ±10%
Product No:
MTL5511
Estimated Lead Time:
Usually ships in 1-7 working days.
Làm nổi bật: 

MTL5511 MTL Safety Barrier

,

9V MTL Safety Barrier

,

MTL safety barrier instrument

Điều khoản thanh toán và vận chuyển
Minimum Order Quantity
1
Giá bán
negotiable
Packaging Details
carton
Delivery Time
on request
Payment Terms
T/T
Supply Ability
100+pc+on stock
Mô tả sản phẩm

MTL5511 MTL Instruments Switch/Proximity Detector Interface

 

The MTLx511 enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous-area

Hazardous-area inputs : Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)

 

Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if an
input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed

 